2024-03-06 16:52:55.00000SHEET PV-10: AC CURRENT LABEL MUST INDICATE MAXIMUM
 COMBINED INVERTER OUTPUT OS 25.41 AMPS WITHOUT THE
 ADDITION OF ANY DEMAND FACTORS. 125% DEMAND FACTORS ARE
 TO BE APPLIED ONLY IN SIZING OVERCURRENT PROTECTION,
 EQUIPMENT RATINGS, AND CONDUCTOR SIZES, SEE 690.54.
 IF POSSIBLE, SUBMIT ONLY THE AFFECTED SHEET, NOT THE
 ENTIRE PLANSET.