2024-02-21 15:30:20.00000SHEET PV3.2: AC CURRENT LABEL TO SHOW ACTUAL MAXIMUM
 COMBINED INVERTER OUTPUT OF 27.83A. DO NOT ADD DEMAND
 FACTOR TO THIS VALUE; THE ADDITION OF A 25% DEMAND
 FACTOR IS INTENDED FOR SIZING CONDUCTORS, EQUIPMENT,
 AND OVERCURRENT PROTECTION ONLY.
 IF POSSIBLE, SUBMIT ONLY THE AFFECTED SHEET PV 3.2, NOT
 THE ENTIRE PLAN SET.