-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 24020568
Permit Number 24020568
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2024-02-21 15:15:35.000001] PROVIDE SPECIFICATION SHEET FOR "MICROGRID
 INTERCONNECTION DEVICE" (ENPHASE SWITCH)
 2] SHOW DISCONNECTING MEANS, READILY ACCESSIBLE AND
 EFFECTIVELY LABELED, FOR BATTERIES ON EXTERIOR OF HOUSE
 3] REPLACE CONDUCTORS BETWEEN ENPHASE SWITCH AND FIRST
 BATTERY TO MINIMUM #8 CU. CONDUCTORS MUST HAVE A
 MINIMUM AMPACITY OF 40 AT 75 DEGREES C.
2024-02-16 11:35:26.00000SENT EMAIL FOR VALUATION AND PLAN REVIEW FEE.