Plan Review Notes For Permit 24020488
Permit Number 24020488
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2024-02-21 14:37:31.00000SHEET PV3.2: AC CURRENT LABEL TO SHOW ACTUAL MAXIMUM
 COMBINED INVERTER OUTPUT OF 39.93A. DO NOT ADD DEMAND
 FACTOR TO THIS VALUE; THE ADDITION OF A 25% DEMAND
 FACTOR IS INTENDED FOR SIZING CONDUCTORS, EQUIPMENT,
 AND OVERCURRENT PROTECTION ONLY.
 IF POSSIBLE, SUBMIT ONLY THE AFFECTED SHEET PV 3.2, NOT
 THE ENTIRE PLAN SET.