Date Text
2024-02-13 15:55:19.00000SHEET PV-3.2: SHOW AC CURRENT LABEL VALUE AS 43.56A,
 NOT 54.45A. CURRENT VALUES SHOULD BE INDICATED AS
 MAXIMUM COMBINED INVERTER OUTPUT WITHOUT THE ADDITION
 OF DEMAND FACTORS. REFERENCE 690.54.
 IF POSSIBLE, SUBMIT ONLY THE AFFECTED SHEET, NOT THE
 ENTIRE PLANSET.
2024-02-13 14:13:39.00000OSCAR.UMANA@MOMENTUMSOLAR.COM