Plan Review Notes
Plan Review Notes For Permit 24010522
Permit Number 24010522
Review Stop BUILDING
Sequence Number 4
Notes
Date Text
2024-04-17 14:41:18.00000SHEET E-1: SHOW EXISTING FEEDER CONDUCTOR SIZE BETWEEN
 SERVICE AND INTERIOR LOAD CENTER; SHOW RATING OF MAIN
 BREAKER SIZE IN INTERIOR LOAD CENTER. THE PV
 INTERCONNECTION SHOWN IS A FEEDER TAP, AND AS SUCH,
 MUST COMPLY WITH 705.12 (B)(1) (A) OR (B).
 OVERCURRENT DEVICES IN THE EXISTING INTERIOR LOAD
 CENTER WILL BE SUPPLIED BY BOTH UTILITY AND SOLAR; AS
 SUCH, THE FEEDERS SUPPLYING THIS LOAD CENTER MUST BE
 PROTECTED ACCORDING TO THEIR AMPACITY OR MUST BE RATED
 FOR THE SUM OF THE FEEDER SUPPLY BREAKER PLUS 125% OF
 THE SOLAR OUTPUT CURRENT.
  