Plan Review Notes For Permit 24010522
Permit Number 24010522
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2024-04-15 08:57:52.00000REVISION SENT IN FROM PERMITS@WEARESOLARPOWERUS.COM,
 CHANGE MADE AFTER INSTALL.
2024-03-06 13:26:39.000001] SHEET E-1: SHOW EXISTING FEEDER CONDUCTOR SIZE
 BETWEEN SERVICE AND INTERIOR LOAD CENTER; SHOW ANY
 EXISTING MAIN BREAKER SIZE IN INTERIOR LOAD CENTER. THE
 PV INTERCONNECTION SHOWN IS A FEEDER TAP, AND AS SUCH,
 MUST COMPLY WITH 705.12 (B)(1).
 2] SHEET E-4: AC CURRENT LABEL AT THE MAIN SERVICE
 PANEL MUST SHOW THE COMBINED PV OUTPUT FROM BOTH
 EXISTING AND PROPOSED SYSTEMS (32.93A). THE AC CURRENT
 LABEL FOR THE PROPOSED PV SYSTEM DISCONNECT MAY SHOW
 THE OUTPUT OF THE PROPOSED SYSTEM ONLY (12.1 A).
2024-02-29 08:42:14.00000PERMITS@WEARESOLARPOWERUS.COM