2024-01-16 17:00:18.00000PLAN REVIEW NOTES: PERMIT #23120808
  
 I HAVE REVIEWED THESE PLANS AND THEN PLANS WILL NEED TO
 BE REVISED TO ADDRESS THE FOLLOWING COMMENTS.
  
 1. THE PLANS WILL NEED TO BE NOTED THAT THE ELECTRICAL
 DEVICES IN THE EXAM ROOMS WILL NEED TO BE INSTALLED TO
 MEET NEC 517.13 REGULATIONS FOR “PATIENT CARE”
 LOCATIONS.
 2. THE DOOR ENTERING BATHROOM #2 WILL MAY NEED TO BE
 REVISED. PLANS DO NOT SHOW MEASUREMENT FROM THE DOOR TO
 THE ADJACENT MECHANICAL CLOSET WALL. THIS DISTANCE MUST
 BE A MINIMUM OF 54”.
 3. AS NOTED IN THE FIRE MARSHALS REPORT, THE FIRE
 EXTINGUISHERS NEED TO BE RELOCATED TO THE EXITS.
 4. THE FIRE MARSHAL ALSO HAS NOTED THAT ADDITIONAL
 EMERGENCY LIGHTING BE ADDED ON THE EXTERIOR AT THE
 EXITS.
 5. ADDITIONAL EMERGENCY LIGHTING IS ALSO NEEDED IN THE
 PROVIDER OFFICE, THE CONFERENCE ROOM, 2 STAFF OFFICES
 AND THE NORTH CORRIDOR.
 6. ADDITIONAL EXIT SIGNAGE NEEDS TO BE ADDED IN THE
 EAST CORRIDOR AT SOUTH END DOOR TO FRONT LOBBY. THIS
 NEEDS TO BE A COMBINATION EMERGENCY/EXIT LIGHT.
 7. A DIRECTIONAL EXIT SIGN NEEDS TO BE ADDED IN THE
 WEST CORRIDOR AT THE SOUTH END DIRECTING TO THE LOBBY
 AREA.
 8. THERE IS ALSO A QUESTION IF THERE IS ROOM FOR A 36”
 GRAB BAR AT THE REAR OF THE WATER CLOSET IN BATHROOM #2
 DUE TO THE WINDOW.
 ERIC R. LONGSHORE
 BUILDING OFFICIAL
  