Plan Review Notes For Permit 23120791
Permit Number 23120791
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2024-02-06 16:42:29.00000SHEET EE-1: INSTALL MAIN BREAKER IN EXISTING INTERIOR
 PANEL TO LIMIT CURRENT TO 200 AMPS (BUS RATING); SHOW
 SIZE OF EXISTING FEEDER CONDUCTORS BETWEEN SERVICE AND
 INTERIOR PANEL; THESE CONDUCTORS MUST HAVE AN AMPACITY
 NOT LESS THAN THE RATING OF THE NEW MAIN BREAKER. SEE
 705.12 (B)(2)(1) OF 2017 NEC.
 SHEET EE-3: INDICATE ACTUAL MAXIMUM COMBINED INVERTER
 OUTPUT ON AC CURRENT LABEL (56.87A).