2023-11-29 16:27:31.00000SHEET C1.3: SHOW CIRCUIT DATA FOR THREE PROPOSED
 WALL-MOUNT DISPENSERS.
 SHEET E2.1: REWORK PANEL SCHEDULE SUMMARY. THE
 FOLLOWING VALUES DO NOT CORRESPOND TO THE INDICATED
 CONNECTED LOAD: TOTAL KVA PER PHASE; TOTAL AMPS PER
 PHASE; TOTAL CONNECTED KVA; TOTAL CONNECTED AMPS; KVA
 AND AMP TOTALS AFTER CONTINUOUS FACTOR ADDED.