2023-11-20 10:12:49.00000SHEET E003: SHOW SIZE OF EXISTING FEEDER CONDUCTORS
 BETWEEN SERVICE AND INTERIOR PANEL. USING A FEEDER TAP
 AS SHOWN, INSTALLATION MUST COMPLY WITH 705.12
 (B)(2)(1): THAT PORTION OF THE FEEDER ON THE LOAD SIDE
 OF THE PV INTERCONNECTION SHALL BE PROTECTED BY 1]
 HAVING AN AMPACITY EQUAL TO 125% OF THE PV OUTPUT
 (39.33) PLUS THE RATING OF THE OVERCURRENT DEVICE
 PROTECTING THE FEEDER (125A) OR 2] BY AN OVERCURRENT
 DEVICE ON THE LOAD SIDE OF THE PV INTERCONNECTION RATED
 NOT GREATER THAN THE AMPACITY OF THE FEEDER.
 IF POSSIBLE, SUBMIT ONLY REVISED SHEET E003, NOT ENTIRE
 PLANSET