Plan Review Notes For Permit 23110517
Permit Number 23110517
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2023-11-20 09:53:26.00000SHEET PV4 DOES NOT DEPICT AN EXTERIOR DISCONNECT SWITCH
 TO INITIATE PV ARRAY RAPID SHUTDOWN AND ESS STANDBY
 MODE. SINCE THE IQ CONTROLLER 2 IS DESIGNED TO ISLAND,
 OPENING THE 100-AMP FUSED DISCONNECT WILL NOT INITIATE
 PV RAPID SHUTDOWN OR PUT THE ENCHARGE 10T INTO STANDBY
 MODE.
 ALL OTHER DESIGN CONSIDERATIONS AND VALUES ARE
 COMPLIANT.
  
 CORRECTION REQUIRED: INSTALL BATTERY DISCONNECT (OR
 REMOTE CONTROL SYSTEM SHUTDOWN SWITCH) ON EXTERIOR OF
 HOUSE AND APPLY APPROPRIATE LABEL TO SAME.
 IF POSSIBLE, SUBMIT ONLY SHEET PV4, NOT ENTIRE PLAN
 SET.