-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 23110413
Permit Number 23110413
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2023-11-14 15:24:23.000001] SHEET E003: SHOW SIZE OF FEEDER CONDUCTORS BETWEEN
 SERVICE AND INTERIOR PANEL(S); SHOW OVERCURRENT
 PROTECTION FOR INTERIOR PANELS. AS A FEEDER-TAP
 INTERCONNECTION, THE INSTALLATION MUST COMPLY WITH
 705.12 (B)(2)(1): THAT PORTION OF THE FEEDER ON THE
 LOAD SIDE OF THE PV INTERCONNECTION SHALL BE PROTECTED
 BY 1) AN AMPACITY NOT LESS THAN THE SUM OF THE 125A
 SOURCE PLUS 125% OF THE PV OUTPUT, OR 2) OVERCURRENT
 PROTECTION ON THE LOAD SIDE OF THE PV INTERCONNECTION
 RATED NOT GREATER THAN THE AMPACITY OF THE FEEDER.
  
 2] SHEET E005: CHANGE AC CURRENT LABEL TO SHOW 13.31
 AMPS
2023-11-13 13:52:04.00000DANIELA.OROZCO@GOSUNERGY.COM
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved