Plan Review Notes For Permit 23110412
Permit Number 23110412
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2023-11-14 14:37:04.00000SHEET E003: NEW 200A LOADCENTER WITH 100A MAIN BREAKER
 IS SPECIFIED; PLEASE PROVIDE LOAD CALCULATION PER NEC
 ARTICLE 220 INDICATING THAT 100 AMP SERVICE IS ADEQUATE
 FOR DEMAND LOAD.