2024-02-06 15:55:33.00000SHEET E-003: SHOW SIZE OF EXISTING FEEDER CONDUCTORS
 BETWEEN SERVICE AND MOBILE HOME. THESE CONDUCTORS MUST
 HAVE A MINIMUM AMPACITY OF 150, BASED ON THE EXISTING
 150A MAIN BREAKER IN THE MOBILE HOME PANEL. 125% OF PV
 INPUT (30.25 A) PLUS SERVICE DISCONNECT RATING (125A)
 EQUALS 155.25A; THIS CURRENT WILL BE LIMITED TO 150A BY
 THE MOBILE HOME PANEL MAIN BREAKER; HOWEVER, THE
 EXISTING FEEDER CONDUCTORS MUST BE RATED AT LEAST 150
 AMPS TO PREVENT OVERCURRENT ON THE FEEDERS.
 ALTERNATIVELY, REPLACE THE MAIN BREAKER IN THE MOBILE
 HOME PANEL WITH A 125A BREAKER.