Plan Review Notes For Permit 23110292
Permit Number 23110292
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2023-11-09 08:49:44.00000STACY.AMEROSA@GOSUNERGY.COM
2023-11-09 08:35:31.00000SHEET E003: SHOW SIZE OF FEEDER CONDUCTORS BETWEEN
 EXTERIOR SERVICE AND INTERIOR MOBILE HOME PANEL. THESE
 CONDUCTORS MUST HAVE AN AMPACITY NOT LESS THAN THE
 RATING OF THE MAIN BREAKER IN THE MOBILE HOME (150A IN
 THIS CASE) WHEN USING LOAD-SIDE PV INTERCONNECTION AS
 SHOWN. REFER TO 705.12 (B)(2)(1).