2023-11-01 16:28:50.00000SHEET E003: SEE 705.12 (B)(2)(1). UNKNOWN SIZE OF
 EXISTING FEEDERS SUPPLYING INTERIOR PANEL. THESE
 FEEDERS MUST HAVE AN AMPACITY OF AT LEAST 125% OF THE
 PV INPUT PLUS 125 AMPS (SERVICE BREAKER) OR THE MAIN
 BREAKER IN THE INTERIOR PANEL MUST BE RATED NO MORE
 THAN THE FEEDER AMPACITY.