Plan Review Notes
Plan Review Notes For Permit 23100682
Permit Number 23100682
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2023-12-20 08:56:47.000001] NEW VALUATION REQUIRED DUE TO ADDITION OF ENERGY
 STORAGE SYSTEM. PROVIDE STATEMENT OF REVISED VALUATION
 ON COMPANY LETTERHEAD.
 2] SHEETS A101 & E601: A READILY ACCESSIBLE AND
 PERMANENTLY IDENTIFIED DISCONNECTING MEANS IS REQUIRED
 ON OR WITHIN SIGHT OF THE ENERGY STORAGE DEVICES. (NOTE
 THAT 2020 NEC REQUIRES THIS DISCONNECTING MEANS TO BE
 ON THE EXTERIOR OF THE HOUSE). REFER TO 2017 NEC 706.7
 (A).
 THE TESLA FACTORY-INSTALLED SWITCH ON EACH BATTERY IS
 ACCEPTABLE FOR THIS PURPOSE PROVIDED THAT IT IS CLEARLY
 AND PERMANENTLY IDENTIFIED PER 2017 NEC 706.7 (E)(5).
 NOTE THAT THIS IDENTIFICATION MUST INCLUDE A DIRECTORY
 OR PLACARD AT ALL DISCONNECTING MEANS (ESS & TESLA
 SWITCH) SHOWING THE LOCATION OF EVERY BATTERY
 DISCONNECTING MEANS.
2023-12-15 10:34:42.00000REVIEW SENT IN 12/14/23