2023-11-20 16:18:52.00000REVISED PLANS INDICATE (13) 385W MODULES PER STRING.
 MODULE VOC (NOMINAL OPERATING CELL TEMPERATURE) =
 41.85. 41.85 X 13 = 544 VDC. MAXIMUM INVERTER INPUT
 VOLTAGE = 480 VDC.
 RECONFIGURE SYSTEM TO LIMIT DC INPUT VOLTAGE AT
 INVERTER TO LESS THAN 480 VOLTS PER STRING.