2023-10-12 14:09:20.00000SHEET PV-4: MAXIMUM SERIES VOC ON STRING #1 EXCEEDS
 MAXIMUM DC INPUT VOLTAGE OF INVERTER. 15 MODULES @
 41.85VOC > 480VDC INVERTER MAXIMUM.
2023-10-10 12:31:40.00000ALREADY PAID FOR PERMIT THE RECEIPT IS 9177250 236.78
 SEE ATTACHMENT