-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 23090709
Permit Number 23090709
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2023-11-22 15:54:10.00000SHEET E003: REVISE ONE-LINE DIAGRAM. THE
 INTERCONNECTION POINT IS A FEEDER TAP, NOT A
 SUPPLY-SIDE TAP. DO NOT SHOW BONDING OF
 NEUTRAL-TO-GROUND IN PV DISCONNECT.
 IF POSSIBLE, SUBMIT ONLY REVISED SHEET E003, NOT ENTIRE
 PLANSET.
2023-11-22 08:51:30.00000REVISED MOUNTS STACY.AMEROSA@GOSUNERGY.COM