Plan Review Notes
Plan Review Notes For Permit 23090358
Permit Number 23090358
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2023-10-06 11:34:07.00000EMAILED FOR PAYMENT
2023-09-19 12:37:18.00000REVISED PLANS RECEIVED 09/19/23
2023-09-14 08:24:32.00000SHEET E003: EQUIPMENT GROUNDING CONDUCTOR BETWEEN NEW
 LOAD CENTER AND PV DISCONNECT MUST BE #6 CU (CONDUCTOR
 ID #4). THIS INTERCONNECTION IS A FEEDER TAP CONNECTED
 ON THE LOAD SIDE OF A 125A OCPD; TABLE 250.122 APPLIES.
 IF POSSIBLE, SEND REVISED SHEET E003 ONLY, DO NOT SEND
 ENTIRE PLANSET.