Plan Review Notes For Permit 23080948
Permit Number 23080948
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2024-03-20 16:42:47.00000SHEET ESPV-3, ENERGY STORAGE DISCONNECTING MEANS MUST
 BE READILY ACCESSIBLE AND EFFECTIVELY IDENTIFIED AS
 FOLLOWS:
 1] INSTALL PLACARD AT UTILITY SERVICE EQUIPMENT
 (ADJACENT TO METER) INDICATING LOCATIONS OF BATTERY
 DISCONNECTS. (SERVICE EQUIPMENT IS LOCATED AROUND
 CORNER FROM ENERGY STORAGE EQUIPMENT).
 2] INSTALL LABELS ON OR IMMEDIATELY ADJACENT TO
 POWERWALLS OR ON FACE OF GATEWAY INDICATING LOCATION(S)
 OF BATTERY DISCONNECTING MEANS.
  
 ENERGY STORAGE DISCONNECTING MEANS MUST COMPLY WITH NEC
 706.15, AND LABELS MUST BE OF SUFFICIENT DURABILITY TO
 WITHSTAND THE ENVIRONMENT, AND NOT BE HANDWRITTEN.
 FACTORY-INSTALLED SWITCHES ON TESLA POWERWALLS MAY BE
 USED AS DISCONNECTS PROVIDED THEY ARE LOCKABLE IN THE
 OPEN POSITION, ARE PROPERLY IDENTIFIED, AND ARE READILY
 ACCESSIBLE.
 ALTERNATIVELY, A REMOTE LOW VOLTAGE DISABLE SWITCH
 (CONNECTED TO AUX TERMINALS IN THE GATEWAY) MAY BE
 INSTALLED TO ACCOMPLISH ENERGY STORAGE SHUT DOWN AND PV
 RAPID SHUTDOWN.
2024-03-20 14:37:31.00000DAGOBERTO MOLINA SENT IN