-     My Account  
   

Log in is not required to search. In the red banner above select: I Want To > Search > Permits

Plan Review Notes
Plan Review Notes For Permit 23080948
Permit Number 23080948
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2023-09-05 12:42:27.00000CDORMAN DISSAPPROVED THE PLANS.
 SENT ME COMMENTS FOR THE CONTRACTOR. ONBASED 9/5
2023-09-01 15:14:52.00000ORIGINAL PV INSTALLATION UNDER PERMIT #21090249
 SPECIFIES IQ7+ MICROINVERTERS (1.21A OUTPUT).
 ALTERATION PLANS FOR ADDING ENERGY STORAGE SPECIFY
 EXISTING IQ7-60 MICROINVERTERS (1.0A OUTPUT).
 VERIFY ACTUAL EXISTING MICROINVERTERS AND MODIFY SHEET
 ESPV-3 AS NECESSARY TO REFLECT EXISTING INSTALLATION.
 THIS VARIABLE WILL AFFECT CONDUCTOR AND OVERCURRENT
 SIZES ON THE PROPOSED INSTALLATION AND MUST BE
 ACCURATELY SHOWN ON NEW PLANS.
2023-08-28 10:37:37.00000MAILED IN BY SUNNOVA
Copyright © 2008 – THE PLUS SERIES ® – All Rights Reserved