Plan Review Notes
Plan Review Notes For Permit 23080733
Permit Number 23080733
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2023-08-23 10:29:25.00000THIS IS CONSIDERED A COMMERCIAL APPLICATION AND
 THEREFORE SUBJECT TO FIRE REVIEW.
 PLANS ARE INCOMPLETE. THE FOLLOWING ITEMS WILL NEED TO
 BE ADDED TO PLANS FOR REVIEW.
 1. EMERGENCY/EXIT COMBO LIGHTS ARE NEEDED IN EACH AREA
 OF THE STRUCTURE. (BOTH BATHROOMS AND STORAGE AREA)
 2. A FIRE EXTHIGUISHER NEEDS TO BE ADDED TO THE PLANS.
 (ONE FIRE EXTINGUISHER LOCATED ON EXTERIOR OF STRUCTURE
 IN A CABINET BY DOORS WILL SUFFICE)
 3. A PLUMBING PAGE NEEDS TO BE ADDED SHOWING PLUMBING
 LAYOUT, WATER HEATER DETAILS AND TRAP PRIMER DETAIL.
 (TRAP PRIMERS ARE REQUIRED FOR THE FLOOR DRAINS.)
 4. AN ADA COMPLIANCE PAGE NEEDS TO BE ADDED TO THE
 PLANS. THIS PAGE NEEDS TO INCLUDE ADA SPECIFICATIONS
 FOR SIGNAGE, BATHROOM DETAILS AND ALL ADA REQUIREMENTS.
 (HEIGHT OF SINKS, CLEAR SPACE OF FIXTIRES, OFFSETS OF
 WATER CLOSETS, GRAB BAR DETAILS ETC.)
 5. AN ELECTRICAL PAGE NEEDS TO BE ADDED TO THE PLANS
 SHOWING PANEL LOCATION (OR SOURCE OF POWER) AND GFCI
 PROTECTED OUTLETS THROUGHOUT.