2023-08-23 16:40:48.000001] TRANSFORMER SECONDARY SHOULD SHOW (3) SETS OF 4 400
 KCMIL, NOT (3) SETS OF 3 400 KCMIL. A NEUTRAL MUST BE
 INCLUDED IN THESE CONDUCTOR SETS.
 2] SHOW 2/0 GROUNDS (SUPPLY-SIDE BONDING JUMPERS) IN
 TRANSFORMER SECONDARY CONDUCTOR SETS AS COPPER. IF
 USING ALUMINUM, INCREASE TO 4/0 IN EACH SET. SEE TABLE
 250.102 (C)(1).
 3] SHOW #3 EQUIPMENT GROUNDING CONDUCTOR IN TRANSFORMER
 PRIMARY CONDUCTOR SETS AS COPPER. IF USING ALUMINUM,
 INCREASE TO #1 IN EACH SET. SEE TABLE 250.122.
 4] SHOW GROUNDING ELECTRODE CONDUCTOR FROM TRANSFORMER
 BONDED TO GROUNDING ELECTRODE SYSTEM AT MAIN 480V
 SERVICE PANEL. SEE 250.30 (A) (4).
 5] PROVIDE BONDING/GROUNDING DETAIL FOR TRANSFORMER
 (INTERIOR CONNECTIONS DETAIL FOR ALL
 GROUNDING/BONDING).