Date Text
2023-11-09 15:56:32.00000SHEET E002: SHOW 50A OVERCURRENT PROTECTION IN PV
 DISCONNECT. 33 X 1.21 X 1.25 = 49.91.
 IF POSSIBLE, SEND REVISED SHEET E002 ONLY, NOT ENTIRE
 PLANSET.
2023-11-09 10:06:08.00000SENT REVISION MATTHEW.WILSON@LUMIO.COM