2023-08-16 12:06:44.00000PREVIOUS DEFICIENCY NOT CORRECTED. SEE SHEET E-003,
 CONDUCTOR SET #4. GROUNDING CONDUCTOR BETWEEN FEEDER
 TAP AND PV DISCONNECT MUST BE MINIMUM #8 COPPER.