2023-08-09 16:19:59.00000SHEET E003: INSTALL #8 BONDING CONDUCTOR BETWEEN LOAD
 SIDE (FEEDER) TAP AND PV DISCONNECT. DO NOT BOND
 NEUTRAL IN PV DISCONNECT. SEE TABLE 250.102 (C)(1) AND
 250.24 (A)(5).
 SUBMIT REVISED E003 OR REVISED SOLAR PLAN SET SHOWING
 CORRECTION.