2023-08-16 16:02:47.00000USE CIVITEK RECEIPT 8668438 FOR 195.78 THEN LET SHANNON
 KNOW HOW MUCH ADDITIONAL SHE OWES FOR THE PAYMENT OF
 THIS PERMIT - SEE ATTACHMENT COPY OF RECEIPT
2023-08-02 13:30:45.00000SHEET 1 (RISER DIAGRAM):
 1] RE-IDENTIFY "SERVICE LATERAL" AS A FEEDER.
 2] ADD #6 CU EQUIPMENT GROUNDING CONDUCTOR TO FEEDER
 SET
 3] INCREASE FEEDER UNGROUNDED CONDUCTORS TO 3/0 CU OR
 DECREASE PROPOSED SERVICE DISCONNECT TO 175A RATING.
 (MAXIMUM AMPACITY OF PROPOSED 2/0 CU IS 175A). THIS
 APPLIES TO ALL FEEDER CONDUCTORS BETWEEN PROPOSED
 SERVICE AND PROPOSED DISTRIBUTION PANEL, AND WILL ALSO
 APPLY TO THE BLOWER CONTROL PANEL CONDUCTORS
 ORIGINATING IN THE DISTRIBUTION PANEL, UNLESS
 OVERCURRENT PROTECTION IS PROVIDED ON THE LOAD END OF
 THESE CONDUCTORS AS A FEEDER TAP PER 240.21 (B)(5).
 4] AS AN ALTERNATIVE TO ITEM #3, PROVIDE A SPECIFIC
 LOAD SUMMARY SHOWING COMPLIANCE WITH 430.24 (FOR 2/0
 CU) AND WITH 430.62 (FOR 200A BREAKER).