2023-08-02 15:08:31.00000SHEET PV4: PV DISCONNECT MUST BE LOCATED ON EXTERIOR OF
 ONE-FAMILY DWELLING TO FUNCTION AS REQUIRED RAPID
 SHUTDOWN SWITCH, 690.12 (C). REMOVE #10 EGC BETWEEN PV
 DISCONNECT AND SUPPLY-SIDE TAP; USE NEUTRAL CONDUCTOR
 FOR SYSTEM BONDING IN PV DISCONNECT.