Date Text
2023-09-12 15:58:25.00000SENT PAYMENT REQUEST 9/12
2023-07-27 15:28:20.00000SHEET PV-6: CONDUCTORS BETWEEN COMBINER PANEL AND
 SUPPLY-SIDE TAP MUST HAVE A MINIMUM AMPACITY OF 68 AMPS
 AT 75 DEGREES C: (45 X 1.21) X 1.25 = 68.07. CHANGE
 CONDUCTORS TO MIN #4 THWN CU.