2023-09-14 16:53:45.00000SHEET E-1, CLARIFICATIONS AND CORRECTIONS REQUESTED:
 1] POSSIBLE CONFLICT WITH ITEM#16. #12 NOTE INDICATES
 150A BUS RATING; ITEM #16 INDICATES 125A BUS RATING FOR
 SAME PANEL. IT IS ASSUMED THE 150A NOTATION IS
 CALCULATING 120% OF THE 125A BUS RATING, PLEASE CLARIFY
 LANGUAGE.
 2] ADD #8 CU EQUIPMENT GROUNDING CONDUCTOR TO CONDUCTOR
 ID #18, FEEDER WITH 100A O/C PROTECTION.
 3] CORRECT NOTATION OF 150A MSP BUS RATING SHOWN IN
 "SYSTEM DATA" BOX IN LOWER RIGHT QUARTER OF SHEET
 (ASSUMING 125A BUS AS INDICATED ON ONE-LINE).
  