Plan Review Notes
Plan Review Notes For Permit 23060146
Permit Number 23060146
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2023-07-19 14:02:18.000001] PLEASE CLARIFY IF THE SCOPE OF WORK IS AN ADDTION TO
 AN EXISTING PV SYSTEM.
 2] STRUCTURAL ENGINEERING HAS BEEN RECEIVED AND IS
 APPROVED.
 3] SHEET E-1:
 A) CONDUCTORS BETWEEN SUPPLY-SIDE TAP AND 125A IQ
 CONTROLLER BREAKER MUST HAVE AN AMPACITY NOT LESS THAN
 125A. AMPACITY SELECTION IS PER 75 DEGREE COLUMN OF
 TABLE 310.15 (B)(16). DWELLING UNIT DERATING DOES NOT
 APPLY SINCE THESE CONDUCTORS DO NOT SUPPLY THE ENTIRE
 DWELLING UNIT.
 B) CONDUCTORS ON THE LOAD SIDE OF THE 100A IQ
 CONTROLLER BREAKER MUST HAVE AN AMPACITY NOT LESS THAN
 100A WITH AMPACITY SELECTION AS IN ITEM (A) ABOVE.
 C) CONDUCTORS "B" AND "C" DESCRIPTION IN LEGEND DO NOT
 CORRESPOND TO THEIR POSITIONS IN THE ONE-LINE DIAGRAM.
 D) "OCPD" VALUES IN LEGEND ARE NOT ACCURATE. SHOW
 INTENDED OVERCURRENT PROTECTION VALUE FOR EACH SET OF
 CONDUCTORS.
 REWORK SHEET E-1 AS NECESSARY FOR CODE-COMPLIANCE AND
 CLARITY.
  
  