Plan Review Notes
Plan Review Notes For Permit 23060146
Permit Number 23060146
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2023-06-08 10:10:06.000001] PROVIDE OWNER AFFIDAVIT WITH APPLICATION PACKAGE
 (OWNER ACTING AS CONTRACTOR)
 2] SHEET S-2 (DETAILS) AND SHEET S-1A (MOUNTING PLAN):
 PROVIDE PROFESSIONAL ENGINEERING SEAL ON AFFECTED
 SHEETS OR BY SEPARATE DOCUMENT.
 3] SHEET E-1: PROVIDE SEPARATE CONDUITS FOR SUPPLY-SIDE
 TAP CONDUCTORS AND PV INPUT CONDUCTORS (DESIGNATION "A"
 ON PLANS). SUPPLY-SIDE TAPPED CONDUCTORS MUST BE
 CONTAINED IN A RACEWAY WITH NO OTHER CONDUCTORS, NEC
 230.7 APPLIES.
2023-06-07 09:58:42.00000OWNER/BUILDER ELECTRIC STATEMENT HAS BEEN RECEIVED, IT
 IS IN ONBASE ALREADY.
2023-06-05 13:48:09.00000EMAILED IN FROM OWNER BRYANAGARD@MSN.COM
 SENT THEM AN OWNERS/ELECTRIC DISCLOSURE STATEMENT TO
 FILL OUT.