Plan Review Notes
Plan Review Notes For Permit 23051281
Permit Number 23051281
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2023-05-31 16:31:33.00000SHEET E01: GROUNDED CONDUCTOR (WHITE WIRE) BETWEEN
 SUPPLY-SIDE TAP AND PV DISCONNECT MUST BE MINIMUM #8 CU
 TO COMPLY WITH TABLE 250.102 (C)(1), SINCE IT IS
 PERFORMING THE FUNCTION OF BONDING THE PV SYSTEM TO
 GROUND. IF INTENDING TO USE #10 UNGROUNDED CONDUCTORS
 FOR SUPPLY-SIDE TAP, PROVIDE DOCUMENTATION OF
 ACCEPTABLE TAP CONDUCTOR SIZES FOR INTENDED TAP DEVICE.
 PLEASE SEND ONLY THE AFFECTED SHEET E01 FOR REVIEW.