Plan Review Notes
Plan Review Notes For Permit 23051246
Permit Number 23051246
Review Stop BUILDING
Sequence Number 2
Notes
Date Text
2023-06-15 16:33:31.00000SHEET E-01: GROUNDED CONDUCTOR (WHITE) BETWEEN
 SUPPLY-SIDE TAP AND PV DISCONNECT MUST BE MINIMUM #8
 CU. SINCE THIS CONDUCTOR WILL BE BONDED IN THE PV
 DISCONNECT, IT SERVES AS THE FAULT CURRENT PATH FOR THE
 SUPPLY-SIDE CONDUCTORS AND MUST BE SIZED PER TABLE
 250.102 (C)(1).