Plan Review Notes
Plan Review Notes For Permit 23051141
Permit Number 23051141
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2023-05-26 12:42:28.00000SHEET E-01: CONDUCTORS BETWEEN PV DISCONNECT AND
 ENPHASE COMBINER PANEL ARE DOUBLE-IDENTIFIED; SHOW
 CORRECT PARAMETERS FOR THIS SET OF CONDUCTORS.
 IDENTIFICATION FOR CONDUCTORS BETWEEN SUPPLY-SIDE TAP
 AND PV DISCONNECT IS MISSING (NOTE THAT THIS MUST BE A
 WIRING METHOD COMPLYING WITH NEC 230.43).