2023-05-25 14:40:10.00000SHEET PV06: IN 100A COMBINER PANEL, USE 60A BREAKER
 WITH EXISTING 10KW INVERTER AC OUTPUT.
 SHEET PV08: AC CURRENT LABEL TO SHOW MAXIMUM COMBINED
 SYSTEM OUTPUT (BOTH EXISTING & PROPOSED SYSTEMS) OF 61
 AMPS