2023-05-17 14:20:07.00000SHEET PV 08: CHANGE AC CURRENT LABEL TO REFLECT MAXIMUM
 SYSTEM OUTPUT OF BOTH EXISTING & PROPOSED ARRAYS (36 X
 1.21 = 43.56 AMPS).
 SHEET PV 06: EXPLAIN NOTE ON CONDUCTOR KEY #4 "NO
 GROUND WIRE PRESENT". THIS RACEWAY SHOULD CONTAIN AN
 EQUIPMENT GROUNDING CONDUCTOR, AND THE NEUTRAL SHOULD
 NOT BE RECONNECTED TO GROUND BEYOND THE INITIAL
 SUPPLY-SIDE DISCONNECT, I.E., DO NOT BOND THE NEUTRAL
 IN THE SECOND DISCONNECT.