2023-09-27 16:17:13.00000SHEET E-1:
 1] CONDUCTOR ID #9 BETWEEN NEW 150A DISCONNECT AND
 GATEWAY IS UNDERSIZED FOR 150A OVERCURRENT PROTECTION.
 PLEASE NOTE THAT TESLA INSTRUCTIONS REQUIRE ALL
 CONDUCTORS ON UTILITY SIDE OF GATEWAY TO BE AT LEAST
 ONE SIZE LARGER THAN THAT REQUIRED BY NEC TO MINIMIZE
 IMPEDANCE.
 2] COMPONENT/CONDUCTOR SCHEDULE AT BOTTOM OF PAGE
 REQUIRES REWORKING. NUMBERS 13-16 HAVE BEEN DUPLICATED
 AND DO NOT ACCURATELY REFLECT WHAT IS SHOWN ON PLAN.