Date Text
2023-07-13 15:22:56.00000REVISION, SHHET E01: SHOW OVERCURRENT PROTECTION IN PV
 DISCONNECT AS 60 AMPS (34 X 1.21 X 1.25 = 51.43) 50A
 FUSES ARE UNDERSIZED FOR 125% OF COMBINED INVERTER
 OUTPUT.
2023-07-13 10:37:06.00000EXPERT SOLAR