2023-02-03 15:31:13.00000VIOLATION OF 2017 NEC 705.12 (B)(2)(3)(B).
 125% OF THE COMBINED INVERTER OUTPUTS PLUS THE RATING
 OF THE MAIN BREAKER EXCEEDS 120% OF THE BUS RATING.
 [(21 X 1.21) X 1.25] + 150 = 181.76.
 150 X 1.2 = 180.
  