Plan Review Notes
Plan Review Notes For Permit 22121072
Permit Number 22121072
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2022-12-22 11:38:26.00000SHEET E1.1: USE MINIMUM 100 AMP FUSES OR CIRCUIT
 BREAKER IN SERVICE DISCONNECT (FIRST POINT OF UTILITY
 DISCONNECT ON LOAD SIDE OF METER). A DWELLING UNIT
 SERVICE DISCONNECT MUST HAVE A MINIMUM RATING OF 100
 AMPS, SEE 230.79 (C).