Plan Review Notes For Permit 22110093
Permit Number 22110093
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2022-11-28 09:26:59.00000RESUBMITTAL OF PLANS - FORWARDED TO CHUCK
 EMAILED IN FROM NELSON CUEVAS
  
2022-11-03 08:05:37.00000SHEET E-1: SPECIFICALLY IDENTIFY THE INTENDED
 MICROINVERTER BY MARKING ON THE SPECIFICATION SHEET.
 SHOWING AS "IQ7" IS NOT SPECIFIC.
  
  
 THE NOTE AT THE LOWER LEFT CORNER OF SHEET E-1
 "MICROINVERTER TOTAL AMPS 26.25" DOES NOT CORRESPOND
 WITH MAXIMUM INVERTER OUTPUT FROM THE SPECIFICATION
 SHEET BASED ON 21 MICROINVERTERS.
  
 SHOW BOTH EXISTING AND PROPOSED MICROINVERTERS; SHOW
 CORRECT COMBINED CURRENT OUTPUT CALCULATION.
  
 NOTE THAT THE 30A OCPD WILL BE UNDERSIZED IF USING ANY
 INVERTERS OTHER THAN THE IQ7-60 (1 AMP). ALL CONDUCTORS
 AND OVERCURRENT DEVICES MUST BE RATED AT LEAST 125% OF
 THE ACTUAL MAXIMUM OUTPUT.
  
 SHEET S-1: FILL IN AC CURRENT/VOLTAGE PARAMETERS ON
 PROPOSED LABELS.
  