Date Text
2022-12-15 13:04:09.00000CONDITIONAL APPROVAL PER APPLICATION OF EXAMINER'S NOTE
 ON SHEET E-1: CONDUCTORS BETWEEN SMART SWITCH AND
 BACK-UP PANEL MUST BE MIN #1 CU (125A OVERCURRENT
 PROTECTION). THESE CONDUCTORS ARE NOT SUBJECT TO
 DERATING PER 310.15 (B)(7).