Date Text
2022-11-03 16:25:26.00000SHEET E-1:
 1] CONDUCTORS BETWEEN PV DISCONNECT AND SMART SWITCH
 (FUSED AT 60A) MUST BE MINIMUM #6 CU.
 2] CONDUCTORS FOR SUPPLY-SIDE TAP AND BETWEEN SMART
 SWITCH AND BACKUP PANEL (FUSED AT 125A) MUST BE MINIMUM
 #1 CU. THESE CONDUCTORS DO NOT SUPPLY THE ENTIRE
 DWELLING UNIT AND ARE NOT SUBJECT TO DERATING PER
 310.15 (B)(7).