Plan Review Notes For Permit 22100358
Permit Number 22100358
Review Stop BUILDING
Sequence Number 5
Notes
Date Text
2023-04-12 16:04:00.00000SHEET E01: CONDUCTORS BETWEEN MAIN SERVICE PANEL AND
 GATEWAY ARE UNDERSIZED FOR 200A OVERCURRENT PROTECTION.
 INCREASE CONDUCTOR SIZE TO 3/0 COPPER, OR REDUCE
 OVERCURRENT PROTECTION TO 150A TO USE INDICATED 1/0
 COPPER CONDUCTORS.
2023-04-10 15:20:23.00000REVISION FROM INTERCONNECTION@SUNVENA.COM