Plan Review Notes For Permit 22100358
Permit Number 22100358
Review Stop BUILDING
Sequence Number 3
Notes
Date Text
2023-03-08 16:02:43.00000SHEET E01: 200A RATED CONDUCTORS BETWEEN EXISTING
 EXTERIOR 200A PANEL AND PROPOSED GATEWAY ARE SHOWN
 TERMINATED INTO A 30A CIRCUIT BREAKER IN THE EXTERIOR
 PANEL.
 1] CORRECT THE OVERCURRENT PROTECTION AND TERMINATION
 METHOD FOR THESE CONDUCTORS
 2] ADD AN EQUIPMENT GROUNDING CONDUCTOR WITH THIS SET
 OF CONDUCTORS (SIZED PER TABLE 250.122)