Plan Review Notes
Plan Review Notes For Permit 22100188
Permit Number 22100188
Review Stop BUILDING
Sequence Number 1
Notes
Date Text
2022-10-06 14:47:38.00000SHEET E-01, CONDUCTORS BETWEEN COMBINER PANEL AND PV
 DISCONNECT: 75 DEGREE AMPACITY OF #10 CONDUCTORS IS
 LESS THAN 125% OF COMBINED INVERTER OUTPUT, TABLE
 310.15 (B) (16). CHANGE CONDUCTORS TO MINIMUM #8.
 (24 X 1.21) X 1.25 = 36.3; #10 AMPACITY @ 75 DEGREES =
 35. AMPACITY OF CONDUCTOR LIMITED TO EQUIPMENT TERMINAL
 TEMPERATURE, 110.14.